Harmonic Resonance
Mode Analysis in dq Domain
Abel A. Taffese, Elisabetta
Tedeschi
2017/04/25
|

Abstrac
Harmonic Resonance Mode Analysis (HRMA) is
a technique developed to study harmonic resonance in a power system. Compared
to conventional resonance analysis techniques, HRMA is a powerful method
that can indicate the origin and the locations most affected by a given
mode
of resonance. The method has been shown to be effective for large scale
resonance studies. However, very simplified models are used for representing
power converters. With the proliferation of power converter interfaced
energy sources in the future power system, there is a need to correctly
model power converters in such studies. The main challenge is to correctly
represent the control loops. The controllers are mostly designed in dq
domain while the study is performed in phase domain. To address this problem,
this paper proposes extension of HRMA to dq domain. Formulation of the
problem in dq domain is presented in detail followed by verification using
simple test cases. A detailed model of a voltage source converter for
the aforementioned analysis is also developed and analysed using the test
cases.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 15) |
| Pages: 167-172 |
Date of Publication: 2017/04/25 |
| ISSN: 2172-038X |
Date of Current Version: |
| REF: 260-17 |
Issue Date: April 2017 |
| DOI:10.24084/repqj15.260 |
Publisher: EA4EPQ |
Authors and affiliations
Abel A. Taffese, Elisabetta Tedeschi
Department of Electric Power Engineering. Norwegian University of Science
of Technology. Trondheim, Norway
Key word
Harmonic Resonance Mode Analysis, HRMA, Resonance, dq,
VSC.
References
[1] S. Ranade and W. Xu, An overview of harmonics modeling and simulation,
IEEE Task Force on Harmonics Modeling and Simulation, p. 1, 2007.
[2] K. M. Hasan, K. Rauma, P. Rodriguez, J. I. Candela, R. S. Muñoz-Aguilar,
and A. Luna, An overview of harmonic analysis and resonances of
large wind power plant, in IECON 2011-37th Annual Conference on
IEEE Industrial Electronics Society. IEEE, 2011, pp. 24672474.
[3] W. Xu, Z. Huang, Y. Cui, and H. Wang, Harmonic resonance mode
analysis, IEEE Transactions on Power Delivery, vol. 20, no. 2, pp.
11821190, Apr. 2005.
[4] Y. Cui and X. Wang, Modal frequency sensitivity for power system
harmonic resonance analysis, IEEE Transactions on Power Delivery,
vol. 27, no. 2, pp. 10101017, 2012.
[5] Z. Huang, Y. Cui, and W. Xu, Application of modal sensitivity
for power system harmonic resonance analysis, IEEE Transactions
on Power Systems, vol. 22, no. 1, pp. 222231, 2007.
[6] M. Esmaili, H. A. Shayanfar, and A. Jalilian, Modal analysis
of power systems to mitigate harmonic resonance considering load models,
Energy, vol. 33, no. 9, pp. 13611368, 2008.
[7] H. A. Brantsæter, Harmonic resonance mode analysis and
application for offshore wind power plants, Masters thesis,
Norwegian University of Science and Technology, Dec. 2015.
[8] M. Molinas, The role of power electronics in distributed energy
systems, in Proceedings of the 5th AIST Symposium on Distributed
Energy Systems, 2008.
[9] B. Bahrani, A. Karimi, B. Rey, and A. Rufer, Decoupled dq-current
control of grid-tied voltage source converters using nonparametric models,
IEEE Transactions on Industrial Electronics, vol. 60, no. 4, pp. 13561366,
2013.
[10] P. Kundur, N. J. Balu, and M. G. Lauby, Power system stability and
control. McGraw-hill New York, 1994, vol. 7.
[11] Y. Cui and W. Xu, Harmonic resonance mode analysis using real
symmetrical nodal matrices, IEEE Transactions on Power Delivery,
vol. 22, no. 3, pp. 19891990, Jul. 2007.
[12] N. Mohan, Advanced Electric Drives: Analysis, Control, and Modeling
Using MATLAB / Simulink. Wiley, 2014. [Online]. Available:
https://books.google.no/books?id=PaULBAAAQBAJ
[13] J. J. Grainger and W. D. Stevenson, Power system analysis. McGraw-Hill,
1994.
[14] W. Xu, Component modeling issues for power quality assessment,
IEEE Power Engineering Review, vol. 21, no. 11, pp. 1217, 2001.

|
|