The influence of
the self-excited induction machine into the electrical grid under
instability situation - Real case measurement
R. Bosch, P. Casals and A.
Serrano
2017/04/25
|

Abstrac
The three phase induction machine is used
in the mainly part of the industry and it requires reactive power from
the grid to start and function. The reactive power consumption is economically
fined so the industries install capacitors in parallel with the motors
and loads. The bank capacitor, gives this reactive power to the machine
in order to improve the cos ö factor in the installation. When a
fault appears in the grid, this machine gives the active power to the
fault, but when the overcurrent relay sets the fault, the induction machine
is already with inertia with electromagnetic and mechanic specific parameters
that originate a non-controlled islanding mode and it provides the power
to the loads on this feeder. Even though several works are published within
the islanding detection, the islanding operation about the induction machine
as a generator in power wind energy applications, nevertheless in the
following we show the motor perspective. The stability of the system in
the time period between the relay opening and the fast reconnection is
out of control, so a complete study a about the electric magnitudes, voltage
and reactive power , active power and frequency and the angle stability
is needed. In this paper we show a real case that appears in a distribution
Medium Voltage (MV) radial network in Spain in a 25 kV feeder and we summarize
the voltage /current wave form and the frequency oscillation.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 15) |
| Pages: 233-238 |
Date of Publication: 2017/04/25 |
| ISSN: 2172-038X |
Date of Current Version: |
| REF: 280-17 |
Issue Date: April 2017 |
| DOI:10.24084/repqj15.280 |
Publisher: EA4EPQ |
Authors and affiliations
R. Bosch(1), P. Casals(1) and A. Serrano(1,2)
1 Department of Electrical Engineering. E.T.S.E.I.B, Polytechnic University
of Catalonia. Barcelona (Spain)
2 Electrica Serosense Distribuidora. Pol. Ind. Panamà. Torres de
Segre (Spain)
Key word
Power Quality, distributed generation, electrical transients,
islanding mode, induction machine, non-synchronism situation.
References
[1] M.Pérez Donsión,
La calidad de la energia eléctrica. Garceta Grupo Editorial, 2016.
[2] A. R. Di Fazio, G. Fusco, and M. Russo, Islanding detection
method based on a Thevenin-like model, IET Gener. Transm. Distrib.,
vol. 9, no. 13, pp. 17471754, 2015.
[3] F. Ji, Y. Li, J. Xiang, and S. Liu, Islanding detection method
based on system identification, IET Power Electron., vol. 9, no.
10, pp. 20952102, 2016.
[4] S. Li, K. El-Arroudi, G. Joós, and A. J. Rodolakis, Islanding
protection of multiple distributed resources under adverse islanding conditions,
IET Gener. Transm. Distrib., vol. 10, no. 8, pp. 19011912, 2016.
[5] R. Anne, F. Katha Basha, R. Palaniappan, K. L. Oliver, and M. J. Thompson,
Reliable Generator Islanding Detection for Industrial Power Consumers
With On-Site Generation, IEEE Trans. Ind. Appl., vol. 52, no. 1,
pp. 668676, 2016.
[6] A. R. Bergen and V. Vittal, Power Systems Analysis. Prentice Hall,
2000.
[7] A. Exposito, Gómez, Análisis y operación de sistemas
de energia eléctrica, Mac. McGraw-Hill,2002.
[8] J. C. Das, Effects of Momentary Voltage Dips on the Operation
of Induction and Synchronous Motors, IEEE Trans. Ind. Appl., vol.
26, no. 4, pp. 711718, 1990.
[9] M. H. Bollen, Understanding Power Quality Problems: Voltage Sags and
Interruptions. Wiley, 2000.
[10] M. H. J. Bollen, Influence of motor reacceleration on voltage
sags, IEEE Trans. Ind. Appl., vol. 31, no. 4, pp. 667674,
1995.
[11] F. P. De Mello and G. W. Walsh, Reclosing Transients in Induction
Motors with Terminal Capacitors, AIEE Rotating Mach. Comm., 1961.
[12] C. Wagner, Self-excitation of induction motors with series
capacitors, Trans. Am. Inst. Electr. Eng., vol. 60, no. 12, pp.
12411247, 1941.
[13] Siemens PSS-SINCAL Power systems analysis Software Available:
https://www.siemens.com

|
|