Analysis of the Impact of the Crowbar Protection
on Short-Circuit Level and
Quality Index
Piedy Del Mar Agamez Arias and Marcus Vinicius
Alves Nunes
2017/04/25
|

Abstract
The accelerted growth of power generation
from renewable sources have taken great importance for planning and operation
of distribution network due to the power supplied to the system from these
sources. The development of technologies that allow exploiting the renewable
resources has led to increase of distributed generation (DG) mainly at
the distribution level. The integration of these DGs provides advantages
to the power system as diversification of energy market and reduction
of CO2 emissions. Nevertheless, disadvantages are also present like variations
of short-circuit current levels, which affects the protections coordination
by causing undesirable interruptions of the power supply to users that
should not be affected. This paper analyses the impact on protection system
and quality service index in a radial distribution network caused by the
variation of
short-circuit current level after the integration of a Doubly Fed Induction
Generator (DFIG) under consideration of crowbar protection (disconnect/reconnect).
As study case, an IEEE 13- node test system was used to simulate a balanced
short-circuit and to evaluate the impacts on protection system and quality
service index.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 15) |
| Pages: 813-818 |
Date of Publication: 2017/04/25 |
| ISSN: 2172-038X |
Date of Current Version: |
|
REF: 473-17
|
Issue Date: April 2017 |
| DOI:10.24084/repqj15.473 |
Publisher: EA4EPQ |
Authors and affiliations
Piedy Del Mar Agamez Arias(1,2) and Marcus Vinicius
Alves Nunes(1)
1. ITEC- Technology Institute - Department of Electrical Engineering,
Federal do Pará University. Guamá (Brazil)
2. INESCTEC - Instituto de Engenharia de Sistemas e Computadores, Tecnologia
e Ciência. PDEEC - University of Porto (Portugal)
Key word
Radial Distribution System; Distribution System Protection;
Protection Coordination; Quality Service Index; Distributed Generation.
References
[1] H. Yazdanpanahi, Y. W. Li, and W. Xu, A New
Control Strategy to Mitigate the Impact of Inverter-Based DGs on Protection
System, IEEE Trans. Smart Grid, vol. 3, no. 3, pp. 14271436,
2012.
[2] REN21, Renewables 2016 Global Status Report, Paris. Anu.
ISBN 978-3-9818107-0-7, p. 272.
[3] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac, Embedded
Generation, United Kingdom: The
Institution of Engineering and Technology, IET. ISBN: 9780852967744, 2000.
[4] R. F. Arritt and R. C. Dugan, Review of the Impacts of Distributed
Generation on Distribution Protection,IEEE Rural Electr. Power Conf.
Asheville, USA, pp. 6974, 2015.
[5] K. Vijeta and D. V. S. . Siva Sarma, Protection of distributed
generation connected distribution system, in 2012 International
Conference on Advances in Power Conversion and Energy Technologies (APCET),
2012, no. Aug., pp. 16.
[6] F. M. Nuro and A. B. Arsoy, Voltage Profile and Short Circuit
Analysis in Distribution Systems with DG, IEEE
Electr. Power Conf. Vancouver, Canadá, pp. 15, 2008.
[7] J. C. Gomez, J. Vaschetti, C. Coyos, and C. Ibarlucea, Distributed
Generation: Impact on Protections and Power Quality, IEEE Lat. Am.
Trans., vol. 11, no. 1, pp. 460465, 2013.
[8] ANEEL, Procedimentos de Distribuição de Energia
Elétrica no Sistema Elétrico Nacional PRODIST, Módulo
8 Qualidade da Energia Elétrica, vol. 1ra Versão.
ANEEL, Brazil, pp. 153, 2008.
[9] CREG, Metodología para el Cálculo de Servicio
de Energía Eléctrica en Sistemas de Transmisión Regional
y/o Distribución Local, Com. Regul. Energía y Gas,
p. 59, 2004.
[10] CREG, Resolución CREG 097 de 2008, Resolución
CREG-097. Colombia, pp. 103121, 2008.
[11] J. Morren and S. W. H. De Haan, Ridethrough of Wind Turbines
with Doubly-Fed Induction Generator During a
Voltage Dip, IEEE Trans. Energy Convers., vol. 20, no. 2, pp. 435441,
2005.
[12] J. Morren and S. W. H. de Haan, Short-Circuit Current of Wind
Turbines With Doubly Fed Induction Generator, IEEE Trans. Energy
Convers., vol. 22, no. 1, pp. 174180, 2007.
[13] M. B. C. Salles, A Study on the Rotor Side Control of DFIG-based
Wind Turbine during Voltage Sags Without
Crowbar System, Int. Conf. Renew. Energy Res. Appl. (ICRERA), 2012,
2012.
[14] G. Cardoso, G. Marchesan, and L. F. F. Gutierres, Recloser-fuse
coordination protection for distributed generation systems: methodology
and priorities for optimal disconnections, 12th IET Int. Conf. Dev.
Power Syst. Prot. Copenhagen, Dinamarca, pp. 12.6812.68, 2014.
[15] H. H. Zeineldin, H. M. Sharaf, D. K. Ibrahim, and E. E.- D. A. El-Zahab,
Optimal Protection Coordination for Meshed Distribution Systems
With DG Using Dual Setting Directional Over-Current Relays, IEEE
Trans. Smart Grid, vol. 6, no. 1, pp. 115123, 2015.
[16] M. Petit, X. Le Pivert, and L. Garcia-Santander, Directional
relays without voltage sensors for distribution networks with distributed
generation: Use of symmetrical components, Electr. Power Syst. Res.,
vol. 80, no. 10, pp. 12221228, 2010.
[17] O. Anaya-Lara, N. Jenkins, J. Ekanayake, P. Cartwright, and M. Hughes,
Wind Energy Generation : Modelling
and Control. United Kingdom: Wiley Publications. ISBN: 9780470714331,
2009.
[18] J. P. A. VIEIRA, Otimização de Controladores
Utilizando Algoritmos Genéticos para Melhoria da Capacidade de
Sobrevivência a Afundamentos de Tensão de Aerogeradores de
Indução Duplamente Excitados Tese Doutorado, Univ.
Fed. do Pará, 2009.
[19] O. Gomis-Bellmunt, A. Junyent-FerrÉ, A. Sumper, and J. Bergas-JanÉ,
Ride-Through Control of a Doubly Fed Induction Generator Under Unbalanced
Voltage Sags IEEE Trans. Energy Convers., vol. 23, no. 4, pp. 10361045,
2008.
[20] Jing He, Qing Li, Shiyao Qin, and Ruiming Wang, DFIG wind turbine
modeling and validation for LVRT behavior, IEEE PES Innovative Smart
Grid Technologies, 2012, pp. 15.
[21] IEEE Std 1547, IEEE Standard for Interconnecting Distributed
Resources with Electric Power Systems, 2009.
[22] MASON, R. The art and science of protective relaying,
United States: General Electric series. ISBN:
0471575526, 1956.
[23] IEEE Distribution System Subcommittee, IEEE 13 Node Test Feeder,
2001.
[24] GENERAL ELECTRIC. Fuse saving schemes in feeder relays,
United States: General Electric, 2002.

|
|