Assessment of Harmonic Contribution of a Photovoltaic
Installation Based on Field Measurements
Morteza Pourarab, Jan Meyer, Robert Stiegler
2017/04/25
|

Abstract
Quantifying harmonic contribution of customer
installations to the voltage distortion in the network is still one of
the main challenges of utilities with respect to power quality, particularly
when integrating large number of renewable energy sources. This paper
discusses different aspect of evaluating the low-order harmonic emission
of a 100 kW photovoltaic (PV) installation consisting of 16 single-phase
inverters. Based on field measurements of one week the harmonic currents
of the installation are analyzed with respect to different operating conditions.
The measured harmonic currents are compared with emission values provided
by the manufacturer as well as emission limits specified in standards.
Finally, different methods for the determination of the contribution of
the PV installation to the voltage distortion in the network are compared.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 15) |
| Pages: 865-870 |
Date of Publication: 2017/04/25 |
| ISSN: 2172-038X |
Date of Current Version: |
|
REF: 498-17
|
Issue Date: April 2017 |
| DOI:10.24084/repqj15.498 |
Publisher: EA4EPQ |
Authors and affiliations
Morteza Pourarab, Jan Meyer, Robert Stiegler
Institute of Electrical Power Systems and High Voltage Engineering. Technische
Universitaet Dresden. (Germany)
Key word
Harmonics, harmonic phase angle, harmonic contribution,
PV installation, summation exponent.
References
[1] Electromagnetic compatibility (EMC) - Part 3-14: Assessment
of emission limits for harmonics, interharmonics, voltage fluctuations
and unbalance for the connection of disturbing installations to LV power
systems, IEC TR Std. 61000-3-14, 2011.
[2] Generators connected to the low-voltage distribution network - Technical
requirements for the connection to and parallel operation with low-voltage
distribution networks, VDE-AR-N 4105, 2011.
[3] M. Aiello, A. Cataliotti, S. Favuzza, G. Graditi, "Theoretical
and experimental comparison of total harmonic distortion factors for the
evaluation of harmonic and interharmonic pollution of grid-connected photovoltaic
systems", IEEE Transactions on Power Delivery, 21(3), 2006, pp. 1390-1397.
[4] R. Arghandeh, A. Onen, J. Jung, D. Cheng, R.P. Broadwater V. Centeno,
"Phasor-based assessment for harmonic sources in distribution networks",
Electric Power Systems Research, 116, 2014, pp. 94-105.
[5] L. Cristaldi and A. Ferrero, "Harmonic power flow analysis for
the measurement of the electric power quality," IEEE Trans. Instrum.
Meas., vol. 44, 1995, pp. 683-685.
[6] Xu, W., Liu, X., Liu, Y. "An investigation on the validity of
power-direction method for harmonic source determination', IEEE Trans.
Power Deliv., 2003, 18, (1), pp. 214-219.
[7] A. pelko, B. Blai?, I. Papi?, M. Pourarab, J. Meyer, X.
Xu and S. Z. Djokic, "CIGRE/CIRED JWG C.4.42: Overview of Common
Methods for Assessment of Harmonic Contribution from Customer Installation,"
in 12th IEEE PES PowerTech Conference, Manchester, 2017.
[8] T. Pfajfar, B. Blai? and I. Papi?, "Methods for estimating
customer voltage harmonic emission levels," ICHQP 2008: 13th International
Conference on Harmonics and Quality of Power, Wollongong, Australia, 2008,
pp. 1-6.
[9] A. Varatharajan, S. Schoettke, J. Meyer, and A. Abart, "Harmonic
Emission of Large PV Installations Case Study of a 1 MW Solar Campus,"
in International conference on Renewable Energies and Power Quality (ICREPQ'14),2014,
pp.1-6.
[10] J. Meyer, A. Blanco Castaneda, M. Domagk, P. Schegner, "Assessment
of Prevailing Harmonic Current Emission in Public Low Voltage Networks,"
in IEEE Transactions on Power Delivery, in press.
[11] R. Stiegler, J. Meyer, P. Schegner and D. Chakravorty, "Measurement
of network harmonic impedance in presence of electronic equipment",
IEEE International Workshop on Applied Measurements for Power Systems
(AMPS), September 2015, Aachen, Germany.

|
|