Faulty Readings
of Static Energy Meters Caused by Conducted Electromagnetic Interference
from a Water Pump
Bas
ten Have, Tom Hartman, Niek Moonen, Cees Keyer, Frank Leferink
2019/07/15
|

Abstract
Conducted electromagnetic interference (EMI)
can affect the energy readings of static energy meters. Lower readings
of static energy meters have been reported in many publications, and higher
readings were found when lighting equipment in combination with a dimmer
was used as a load. In this paper it is shown that by using an off the
shelf water pump as a consumer, faulty deviations on the static meters
with respect to a reference meter can be found. In the most extreme case,
using a standard mains supply, deviations between -61% and +2675% were
found. When an ideal power supply with a standardized mains impedance
was used deviations between -19% and +483% were shown to exist.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 17) |
| Pages: 15-19 |
Date of Publication: 2019/07/15 |
| ISSN: 2172-038X |
Date of Current Version:2019/04/10 |
| REF: 205-19 |
Issue Date: July 2019 |
| DOI:10.24084/repqj17.205 |
Publisher: EA4EPQ |
Authors and affiliations
Bas ten Have1, Tom Hartman1, Niek Moonen1, Cees Keyer1,2,
Frank Leferink1,3
1. University of Twente, Enschede, The Netherlands
2. University of Applied Sciences, Amsterdam, The Netherlands
3. Thales Nederland B.V., Hengelo, The Netherlands
Key words
Static Meter, Smart Meter, Electronic Meter, Conducted
Interference, Electromagnetic Compatibility
References
[1] K. Murakawa, N. Hirasawa, H. Ito, and Y. Ogura, Electromagnetic
interference examples of telecommunications systems in the frequency range
from 2kHz to 150kHz, pp. 581-584, 2014.
[2] F. Leferink, Conducted interference, challenges and interference
cases, IEEE Electromagnetic Compatibility Magazine, vol 4, no. 1,
pp. 78-85, 2015.
[3] J. Kirchhof and G. Klein, EMV Grenzwertlüke
wechselrichter stört zähler, 24. Symposium Photovoltaische
Solarenergy, Bad Staffelstein, 2009.
[4] J. Kirchhof, Grenzwertlücke Wechselrichter stört
elektrizitätzähler, EMV, Düsseldorf, 2010.
[5] F. Leferink, C. Keyer, and A. Melentjev, Runaway energy meters
due to conducted electromagnetic interference, IEEE International
Symposium on Electromagnetic Compatibility, pp. 172-175, 2016.
[6] F. Leferink, C. Keyer, and A. Melentjev, Static energy meter
errors caused by conducted electromagnetic interference, IEEE Electromagnetic
Compatibility Magazine, vol. 5, no. 4, pp. 49-55, 2016.
[7] C. Keyer and F. Leferink, Conducted interference on smart meters,
IEEE International Symposium on Electromagnetic Compatibility, pp. 608-611,
2017.
[8] R. Quijano Cetina, A. J. Roscoe, and P.S. Wright, Challenges
for Smart Electricity Meters due to Dynamic Power Quality Conditions of
the Grid: A Review, AMPS 2017 IEEE International Workshop
on Applied Measurements for Power Systems, Proceedings, 2017.
[9] R. Masnicki, Some Remarks on the Accuracy of Energy Meters,
2018 IEEE International Conference on Environment and Electrical Engineering
and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC/I&CPS
Europe), 2018.
[10] B. Have, C. Keyer, and F. Leferink, Monitoring of Power Measured
by Static Energy Meters for Observing EMI Issues, 2018 International
Symposium on Electromagnetic Compatibility (EMC Europe), pp. 903-907,
2018.
[11] IEC 61000-4-11:2004(E), Electromagnetic compatibility (EMC)
part 4-11: Testing and measurement techniques- Voltage dips, short interruptions
and voltage variations immunity tests.

|
|