Islanding Detection
Method for Inverter-Based Distributed Generation by Injecting
Second Order Harmonic Current
Byung-Moon Han
2019/07/15
|

Abstract
This paper proposes a new islanding detection
scheme for the inverter-based distributed generator by injecting negligible
amount of the 2nd order harmonic current. A proportional resonant controller
was used for the output current control of the inverter, and a proportional
resonant filter was used
for extracting the 2nd order harmonic voltage at the point of common coupling
(PCC). The islanding state can be detected by measuring the magnitude
ratio of the 2nd order harmonic voltage to the fundamental voltage when
the 2nd order harmonic current with 0.8% magnitude is injected.
| Published in: Renewable Energy
& Power Quality Journal (RE&PQJ, Nº. 17) |
| Pages: 80-84 |
Date of Publication: 2019/07/15 |
| ISSN: 2172-038X |
Date of Current Version:2019/04/10 |
| REF: 226-19 |
Issue Date: July 2019 |
| DOI:10.24084/repqj17.226 |
Publisher: EA4EPQ |
Authors and affiliations
Byung-Moon Han
Dept. of Electrical Engineering. Myongji University. Yongin, Korea
Key words
Inverter-based distributed generation (DG), Islanding
detection, 2nd order harmonic current injection, Proportional resonant
(PR) controller, Proportional resonant filter
References
[1] Liu F, Kang Y, Zhang Y, et al. Improved SMS
islanding detection method for grid-connected converters,
Renewable Power Generation, 4(1): pp. 36-42, 2010.
[2] Youngseok Jung, Jaeho Choi, and G. Yu, A Novel Active Anti-islanding
Method for Grid-connected Photovoltaic
Inverter, Journal of Power Electronics, Vol. 7, No. 1 p. 64-71,
2007.
[3] Zhihui Dai; Zhiqiang Chong; Xuan Liu; Chuan Li, "Active islanding
detection method based on grid-connected
photovoltaic inverter and negative sequence current injection," Power
System Technology (POWERCON), 2014 International Conference on , pp.1685,1690,
20-22 Oct. 2014
[4] H. Karimi, A. Yazdani and R. Iravani, "Negative-Sequence Current
Injection for Fast Islanding Detection of a
Distributed Resources," IEEE Trans. on Power Electronics, vol. 23,
no. 1, Jan. 2008.
[5] D. Reigosa, F. Briz, C. Charro, P. Garcia, and M. Guerrero, "Active
Islanding Detection Using High-Frequency Signal
Injection," IEEE Trans. on Industry Application, vol. 48, no. 5,
pp. 15881597, Sept./Oct. 2012.
[6] R. Teodorescu and F. Blaabjerg, Proportional-resonant controllers.
A new breed of controllers suitable for gridconnected voltage-source converters,
in Proc. OPTIM, 2004, vol. 3, pp. 914.

|
|